| Rating environment | Standardized chiller rating point | Entering condenser water: 85°F (29.4°C); leaving chilled water: 44°F (6.7°C) | Entering outdoor air: 95°F (35°C); leaving chilled water: 44°F (6.7°C) | Use the applicable AHRI rating condition when comparing published capacity and efficiency. |
| Cooling capacity basis | Normalized example: 500 refrigeration tons | 500 RT = approximately 1,758 kW of cooling, subject to equipment selection | 500 RT = approximately 1,758 kW of cooling, subject to equipment selection | The condenser type does not automatically determine capacity; compressor size, refrigerant, evaporator conditions, and fouling allowance also matter. |
| Typical full-load input | Representative range for large comfort-cooling chillers at the stated rating point | 0.55–0.65 kW/RT; approximately 275–325 kW for a 500 RT example | 0.85–1.05 kW/RT; approximately 425–525 kW for a 500 RT example | Water-cooled equipment generally requires less chiller compressor power at the common AHRI rating point. |
| Full-load COP | COP = cooling capacity ÷ electrical input; 1 RT = 3.517 kW | Approximately 5.4–6.4 COP, based on the representative input range | Approximately 3.3–4.1 COP, based on the representative input range | A higher COP indicates lower chiller-only power at the specified rating condition. |
| Condenser heat rejection | Heat rejected is approximately cooling load plus compressor input | Approximately 2,033–2,083 kW for a 500 RT example, before tower and pump power | Approximately 2,183–2,283 kW for a 500 RT example, discharged directly to outdoor air | Water-cooled systems reject heat through a cooling tower or other heat-rejection device; air-cooled systems require outdoor airflow and coil surface area. |
| Part-load efficiency | Evaluate IPLV/NPLV or application-specific operating points, not full-load COP alone | Often favorable where condenser-water temperature can be reset downward during cool weather | Efficiency varies strongly with outdoor dry-bulb temperature and fan control | Use annual load hours, weather data, and actual entering-water or entering-air temperatures for lifecycle comparison. |
| Water consumption | Project-specific cooling-tower operating condition | Requires condenser-water circulation and typically consumes makeup water through evaporation, blowdown, and drift | No cooling-tower makeup water is required | Choose water-cooled equipment when energy savings justify water treatment, water availability, and maintenance requirements. |
| Installation footprint | Depends on the selected chiller and heat-rejection arrangement | Usually requires a separate cooling tower, condenser-water pumps, water treatment, and service access | Usually requires larger outdoor coil and fan assemblies but no cooling tower loop | Compare total plant space, structural loading, acoustics, piping, and maintenance access rather than chiller dimensions alone. |
| Best-fit application | Selection should reflect climate, load profile, water availability, and operating cost | Large or continuously operating facilities where high efficiency and stable heat rejection are priorities | Projects with limited water availability, simpler installation requirements, or smaller and intermittent loads | Water-cooled condensers are most attractive when long annual operating hours and lower chiller energy use outweigh added system complexity. |